LEX55
LEX55 Ex ec certified RTD sensor for zone 2 and 22
Specifications
| ATEX execution | II 3 G Ex ec IIC T6...T1 Gc |
| ATEX certificate | DEKRA 18ATEX0024 X |
| IECEx execution | Ex ec IIC T6...T1 Gc |
| IECEx certificate | IECEX DEK 17.0046X |
| Suitable for zone | 2 and 22 |
| Ingress protection | IP65 / IEC529 |
| Ambient temp. range | -45°C...+80°C, this can be limited depending on the materials applied such as cables, connection heads, junction boxes and transmitters. |
| Model | DAN-AK (showed), other Ex certified heads possible |
| Material | Aluminium, plastic or stainless steel |
| Cable entry | M20x1.5 standard, other threads possible |
| Construction | Springloaded and replaceable |
| Springaction | >10mm standard, >40mm optional |
| Diameter | 6.0mm standard, other diameters possible |
| Type | Mineral insulated (MgO) |
| Execution | Single or Duplex Pt100 |
| Connection | 3-wire standard, 4-wire optional |
| Accuracy | According IEC 60751 Cl. B, A or AA |
| Measuring range | -20°C...+400°C standard, -220°C...+600°C optional |
| Type | Nipple - union - nipple standard, other constructions possible |
| Material | Stainless steel |
| Style / Connection | 1/2"NPT standard, other threads possible |
| Length | 150 mm standard, other lengths possible |
| The LEX55 is the replacement for the LEX45 Ex nA | |
| This datasheet is purely indicative, build-up of model code may vary from this datasheet |
Customisation possibilities
You can remark the customisation in your quote
| Productcode | LEX55 |
|---|---|
| Sensor S or D | … |
| Class B, A or AA | … |
| Length "U" in mm | … |
| Length "X" in mm | … |